AC Unit Wire Sizing: Electrical Code, Calculations & Selection Guide

Choosing the right wire size for an air conditioning (AC) unit is crucial for safety, efficiency, and meeting electrical code. Incorrect wire sizing can lead to performance issues, fire risk, or voided warranties. This article covers all aspects of selecting the correct wire size for different AC units, based on U.S. standards, helping homeowners and professionals make informed decisions for upgrades or installations.

AC Wire Size Quick Reference Table

AC Unit Size (Tons) Approx. BTUs Max Circuit Amps Recommended Copper Wire Gauge (AWG) Common Breaker Size
1.5-2 18,000–24,000 12–15 14 15–20A
2.5–3 30,000–36,000 15–20 12 20–25A
3.5–4 42,000–48,000 20–30 10 30–35A
5 60,000 30–40 8 35–50A

Understanding Wire Sizing For AC Units

Wire size refers to the diameter of the electrical conductor, measured in American Wire Gauge (AWG). The right size is critical to handle the current—that’s the load—drawn by your AC unit safely. Undersized wires can overheat, potentially causing fires, while oversizing can be unnecessarily costly and hard to manage.

Why Wire Size Matters

  • Safety: Prevents electrical fires and equipment damage.
  • Efficiency: Reduces voltage drop ensuring the AC runs properly.
  • Code Compliance: Meets the National Electrical Code (NEC) standards.
  • Warranty Validity: Many AC manufacturers require proper installation for warranty coverage.

National Electrical Code (NEC) Guidelines

The NEC provides detailed standards for wire sizing. For AC units, NEC Article 440 covers the requirements. The key factors include unit amp rating, wire type (copper or aluminum), ambient temperature, and run length.

  • Minimum Circuit Ampacity (MCA): The minimum wire ampacity required for the equipment (from AC’s nameplate or manual).
  • Maximum Fuse or Circuit Breaker Size: Also provided on the unit label.
  • Voltage Drop: NEC recommends a maximum 3% voltage drop for branch circuits, especially if wire runs are longer than 50 feet.

AC Unit Nameplate: Key To Proper Wire Sizing

Every residential or commercial AC unit has a rating plate providing essential information for choosing wire size, including:

  1. Voltage (such as 208/230V)
  2. MCA (Minimum Circuit Ampacity)
  3. MOCP (Maximum Overcurrent Protection or breaker size)

Use the MCA for wire size calculations and MOCP for breaker selection to ensure compliance and operational safety.

Copper Vs. Aluminum Wire: Which To Choose?

Both copper and aluminum conductors are allowed, though copper is preferred for its higher conductivity, strength, and reliability. If using aluminum, a larger wire is required. Here’s a comparison:

Wire Material Pros Cons
Copper Better conductivity, compact size, easy to install Higher cost
Aluminum Lower cost, lighter weight Requires larger size, subject to corrosion, stricter installation rules

How To Calculate Wire Size For Your AC Unit

  • Step 1: Find the MCA on the AC’s nameplate.
  • Step 2: Select a wire gauge that meets or exceeds the MCA (refer to wire ampacity tables).
  • Step 3: Adjust for run length. If over 50 feet, consider upsizing the wire by one gauge to minimize voltage drop.
  • Step 4: Choose copper for standard installations.

Common Wire Sizes And Their Ampacities (Copper, 60°C/75°C Insulation)

AWG Maximum Amps
14 15
12 20
10 30
8 40
6 55

Reference: Cerrowire Ampacity Charts.

Call 888-906-9139 for Free Local HVAC Quotes – No Obligation, Just Savings!

Typical Wire Sizes For Different AC Units

  • 1.5–2 tons (18,000–24,000 BTU): 14 AWG copper (up to 15A), for units with MCA up to 15.
  • 2.5–3 tons (30,000–36,000 BTU): 12 AWG copper (up to 20A).
  • 3.5–4 tons (42,000–48,000 BTU): 10 AWG copper (up to 30A).
  • 5 tons (60,000 BTU): 8 AWG copper (up to 40A).

Always verify with the AC unit’s nameplate and the NEC for special conditions.

Wire Type And Insulation Ratings

The wire used should be listed for use in wet or outdoor environments if installed outside. Common types include:

  • THHN/THWN: Indicates temperature and moisture resistance, ideal for conduit runs.
  • UF-B: For direct burial or outdoor use, suitable for underground runs.

Insulation must be rated for at least 75°C for most modern equipment to ensure thermal overload protection.

Breaker Sizing And Wire Protection

Select a circuit breaker that does not exceed the MOCP on the unit’s label. For most installations, the breaker should be matched to the wire gauge—for example, 20A breaker with 12 AWG, 30A with 10 AWG.

Overcurrent protection ensures wire is never overloaded beyond its ampacity.

Voltage Drop For Long Wire Runs

Long distances can cause significant voltage drops, reducing efficiency and damaging components. If your AC is more than 50 feet from the panel, use one size larger wire to compensate. For runs over 100 feet, a voltage drop calculator is recommended (Southwire Voltage Drop Calculator).

Permits, Inspections, And Safety Tips

Installations should follow local codes and permitting requirements. Most areas require inspection. If unsure, working with a licensed electrician ensures code-compliance and avoids future safety risks. Always turn off power at the main breaker before working on any electrical component.

Call 888-906-9139 for Free Local HVAC Quotes – No Obligation, Just Savings!

Frequently Asked Questions

What size wire for a 3-ton AC unit?

Most 3-ton units (MCA 15–20A) require 12 AWG copper wire. Verify the label for the exact ampacity.

Do I need a neutral wire for an AC unit?

Standard 240V AC units typically do not require a neutral, only two hots and a ground.

Can I use aluminum wire?

Aluminum is permitted, but must be upsized one gauge compared to copper and installed with anti-oxidant paste per code.

Should I upsize wire for future upgrades?

If anticipating larger equipment, install a larger gauge now to avoid future rewiring.